CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor

Place of Origin Shanghai, China
Brand Name Carlyle
Certification CE
Model Number Describe
Minimum Order Quantity 1
Price Consult
Packaging Details Pallet packaging
Delivery Time 15
Payment Terms L/C, D/A, D/P, T/T, Western Union, MoneyGram
Supply Ability 1000 Piece/Pieces per Year
Product Details
Refrigerant R404A Power Supply 220V380V460V575V-3PH/50HZ/60HZ
Nominal HP Describe Quality Assurance A Year
Leave a Message
Product Description

06DR03136   R404A/R507 Refrigerants

Physical Data
Model Nominal HP Displ. CFM No. of Cylinders Suction Line Size (in) Discharge Line Size (in) Shipping Weight (lbs) Oil Charge (pints)
06DR316 5 15.9 4 1 1/8 5/8 235 4 1/2

 

Available Voltages
208/230-3-60
460-3-60
575-3-60

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 0

 

Tabular Data Summary – Fixed RGT = 65°F Subcooling = 0°F Voltage: 460-3-60Hz
Saturated Condensing Temperature (F) -10 -5 0 5 10 15 20 25
90 Capacity (Btu/hr) 31813 36341 41270 46619 52407 58656 65384 72611
Power (kW) 4 4.21 4.41 4.61 4.78 4.95 5.1 5.23
EER (BTU/WATT-HR) 7.96 8.63 9.35 10.12 10.96 11.86 12.83 13.88
Current (AMPS) 6.39 6.64 6.86 7.07 7.25 7.41 7.54 7.65
110 Capacity (Btu/hr) 26084 30002 34276 38925 43969 49428 55320 61668
Power (kW) 4.4 4.68 4.96 5.23 5.48 5.72 5.95 6.16
EER (BTU/WATT-HR) 5.93 6.4 6.91 7.45 8.02 8.64 9.3 10.02
Current (AMPS) 6.86 7.18 7.49 7.77 8.03 8.27 8.48 8.66
130 Capacity (Btu/hr) 19953 23206 26767 30656 34894 39498 44490 49889
Power (kW) 4.69 5.06 5.42 5.77 6.11 6.43 6.74 7.04
EER (BTU/WATT-HR) 4.26 4.59 4.94 5.31 5.71 6.14 6.6 7.09
Current (AMPS) 7.19 7.6 8 8.37 8.72 9.04 9.33 9.6

 

 

06DR820   R404A/R507 Refrigerants

Physical Data
Model Nominal HP Displ. CFM No. of Cylinders Suction Line Size (in) Discharge Line Size (in) Shipping Weight (lbs) Oil Charge (pints)
06DR820 6.5 20 4 1 3/8 7/8 260 5 1/2

 

Available Voltages
208/230-3-60
460-3-60
575-3-60

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 1

 

Tabular Data Summary – Fixed RGT = 65°F Subcooling = 0°F Voltage: 460-3-60Hz
Saturated Condensing Temperature (F) -10 -5 0 5 10 15 20 25 30 35
90 Capacity (Btu/hr) 42781 48728 55194 61996 69658 77968 86974 96722 107261 118638
Power (kW) 5.24 5.52 5.79 6.08 6.28 6.46 6.61 6.73 6.83 6.91
EER (BTU/WATT-HR) 8.16 8.82 9.54 10.2 11.09 12.07 13.16 14.37 15.7 17.17
Current (AMPS) 8.47 8.78 9.09 9.5 9.73 9.94 10.14 10.3 10.41 10.46
110 Capacity (Btu/hr) 35383 40544 46168 52151 58790 65960 73709 82084 91133 100903
Power (kW) 5.75 6.13 6.49 6.89 7.22 7.52 7.8 8.04 8.26 8.46
EER (BTU/WATT-HR) 6.15 6.62 7.12 7.57 8.14 8.77 9.45 10.2 11.03 11.93
Current (AMPS) 9.03 9.46 9.9 10.4 10.76 11.12 11.48 11.81 12.11 12.36
130 Capacity (Btu/hr) 27398 31694 36392 41215 46669 52536 58861 65692 73077 81063
Power (kW) 6.11 6.58 7.04 7.47 7.95 8.41 8.84 9.23 9.6 9.94
EER (BTU/WATT-HR) 4.49 4.82 5.17 5.52 5.87 6.25 6.66 7.11 7.61 8.16
Current (AMPS) 9.45 10.01 10.58 11.09 11.64 12.2 12.77 13.33 13.87 14.37

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 2

 

 

 

06DR071235 R404A/R507 Refrigerants

Physical Data
Model Nominal HP Displ. CFM No. of Cylinders Suction Line Size (in) Discharge Line Size (in) Shipping Weight (lbs) Oil Charge (pints)
06DR725 6.5 23.9 6 1 3/8 7/8 310 8

 

Available Voltages
208/230-3-60
460-3-60
575-3-60

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 1

 

Tabular Data Summary – Fixed RGT = 65°F Subcooling = 0°F Voltage: 460-3-60Hz
Saturated Condensing Temperature (F) -10 -5 0 5 10 15 20 25
90 Capacity (Btu/hr) 47056 53796 61116 70355 79696 89905 101045 113177
Power (kW) 5.93 6.31 6.68 7.05 7.32 7.57 7.79 7.97
EER (BTU/WATT-HR) 7.94 8.53 9.15 9.98 10.88 11.87 12.97 14.19
Current (AMPS) 9.2 9.64 10.09 11.4 11.81 12.14 12.42 12.63
110 Capacity (Btu/hr) 38397 44261 50643 57819 65728 74347 83738 93963
Power (kW) 6.33 6.81 7.29 7.84 8.29 8.7 9.08 9.41
EER (BTU/WATT-HR) 6.07 6.5 6.95 7.38 7.93 8.54 9.22 9.98
Current (AMPS) 9.66 10.24 10.83 12.43 13.02 13.51 13.93 14.27
130 Capacity (Btu/hr) 29132 34026 39371 44629 50977 57874 65381 73560
Power (kW) 6.53 7.13 7.72 8.25 8.91 9.53 10.11 10.63
EER (BTU/WATT-HR) 4.46 4.77 5.1 5.41 5.72 6.07 6.47 6.92
Current (AMPS) 9.92 10.64 11.39 12.98 13.69 14.31 14.82 15.26

 

 

06DR228 R404A/R507 Refrigerants

Physical Data
Model Nominal HP Displ. CFM No. of Cylinders Suction Line Size (in) Discharge Line Size (in) Shipping Weight (lbs) Oil Charge (pints)
06DR228 7.5 28 6 1 5/8 7/8 315 8

 

Available Voltages
208/230-3-60
460-3-60
575-3-60

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 4

 

Tabular Data Summary
Saturated Condensing Temperature (F) -10 -5 0 5 10 15 20 25 30
90 Capacity (Btu/hr) 58164 65789 74010 85607 96399 108150 120932 134818 149878
Power (kW) 7.2 7.54 7.83 8.62 8.93 9.21 9.45 9.65 9.81
EER (BTU/WATT-HR) 8.07 8.73 9.46 9.93 10.79 11.75 12.8 13.97 15.28
Current (AMPS) 12.42 12.83 13.18 13.61 14.1 14.61 15.11 15.56 15.93
110 Capacity (Btu/hr) 48876 55680 63005 71637 80883 90910 101789 113592 126391
Power (kW) 7.97 8.49 8.96 9.65 10.16 10.63 11.06 11.44 11.79
EER (BTU/WATT-HR) 6.13 6.56 7.03 7.42 7.96 8.56 9.21 9.93 10.72
Current (AMPS) 13.37 13.96 14.49 15.65 16.73 17.87 19.05 20.22 21.34
130 Capacity (Btu/hr) 38215 44084 50399 56420 63940 72058 80845 90372 100712
Power (kW) 8.41 9.12 9.8 10.32 11.06 11.75 12.4 13.01 13.57
EER (BTU/WATT-HR) 4.54 4.83 5.14 5.47 5.78 6.13 6.52 6.95 7.42
Current (AMPS) 13.87 14.67 15.4 17.06 19.15 21.34 23.6 25.89 28.19

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 5

 

 

06DR337   R404A/R507 Refrigerants

Physical Data
Model Nominal HP Displ. CFM No. of Cylinders Suction Line Size (in) Discharge Line Size (in) Shipping Weight (lbs) Oil Charge (pints)
06DR337 10 37.1 6 1 5/8 1 1/8 325 8

 

Available Voltages
208/230-3-60
460-3-60
575-3-60

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 6

 

Tabular Data Summary – Fixed RGT = 65°F Subcooling = 0°F Voltage: 460-3-60Hz
Saturated Condensing Temperature (F) -10 -5 0 5 10 15 20 25
90 Capacity (Btu/hr) 77514 87951 99448 113438 127721 143270 160182 178554
Power (kW) 9.85 10.47 11.07 11.42 11.83 12.2 12.52 12.78
EER (BTU/WATT-HR) 7.87 8.4 8.98 9.93 10.79 11.74 12.8 13.97
Current (AMPS) 14.55 15.33 16.14 17.03 17.76 18.41 18.97 19.44
110 Capacity (Btu/hr) 63193 71823 81363 94900 107100 120361 134779 150451
Power (kW) 10.71 11.47 12.24 12.79 13.46 14.08 14.65 15.16
EER (BTU/WATT-HR) 5.9 6.26 6.65 7.42 7.96 8.55 9.2 9.92
Current (AMPS) 15.64 16.65 17.73 18.41 19.43 20.41 21.32 22.16
130 Capacity (Btu/hr) 49029 55833 63393 74787 84733 95527 107267 120049
Power (kW) 11.38 12.28 13.19 13.68 14.65 15.57 16.42 17.22
EER (BTU/WATT-HR) 4.31 4.55 4.81 5.47 5.78 6.14 6.53 6.97
Current (AMPS) 16.54 17.78 19.11 19.4 20.65 21.88 23.08 24.24

 

06DR541   R404A/R507 Refrigerants

Physical Data
Model Nominal HP Displ. CFM No. of Cylinders Suction Line Size (in) Discharge Line Size (in) Shipping Weight (lbs) Oil Charge (pints)
06DR541 15 41 6 1 5/8 1 1/8 325 8

 

Available Voltages
208/230-3-60
460-3-60
575-3-60

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 7

 

Tabular Data Summary – Fixed RGT = 65°F Subcooling = 0°F Voltage: 460-3-60Hz
Saturated Condensing Temperature (F) -10 -5 0 5 10 15 20 25 30
90 Capacity (Btu/hr) 86072 97732 110583 124705 140175 157071 175471 195454 217097
Power (kW) 11.13 11.75 12.35 12.94 13.51 14.06 14.57 15.05 15.48
EER (BTU/WATT-HR) 7.74 8.32 8.95 9.63 10.37 11.17 12.04 12.99 14.02
Current (AMPS) 17.9 18.49 19.05 19.6 20.14 20.65 21.14 21.61 22.06
110 Capacity (Btu/hr) 70070 79724 90368 102080 114938 129021 144407 161174 179399
Power (kW) 12.07 12.84 13.61 14.38 15.14 15.88 16.61 17.3 17.97
EER (BTU/WATT-HR) 5.81 6.21 6.64 7.1 7.59 8.12 8.7 9.31 9.98
Current (AMPS) 18.79 19.51 20.23 20.95 21.67 22.38 23.09 23.78 24.47
130 Capacity (Btu/hr) 54141 61708 70058 79269 89419 100586 112847 126280 140963
Power (kW) 12.82 13.74 14.67 15.6 16.54 17.47 18.4 19.31 20.21
EER (BTU/WATT-HR) 4.22 4.49 4.78 5.08 5.41 5.76 6.13 6.54 6.98
Current (AMPS) 19.49 20.36 21.24 22.13 23.03 23.94 24.85 25.78 26.71

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 8

 

 

 

06DM808   R404A/R507 Refrigerants

Physical Data
Model Nominal HP Displ. CFM No. of Cylinders Suction Line Size (in) Discharge Line Size (in) Shipping Weight (lbs) Oil Charge (pints)
06DM808 3 8 2 7/8 5/8 160 3

 

Available Voltages
208/230-3-60
460-3-60
575-3-60

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 9

 

Tabular Data Summary - Fixed RGT=65°FSubcooling= 0°F Voltago:460-3-60Hz
Saturated condensing
Temperature (F)
5 10 15 20 25 30 35 40 45 50
90 Capacity (Btu/hr) 21727 24869 28315 32088 36208 40699 45581 50877 56610 62800
Power (kW) 2.48 2.59 2.68 2.75 2.82 2.88 2.93 2.96 2.99 3.01
EER (BTU/WATT-HR) 8.74 9.62 10.59 11.65 12.83 14.14 15.58 17.17 18.93 20.87
Current (AMPS) 5.61 5.86 6.09 6.29 6.46 6.6 6.71 6.78 6.82 6.82
110 Capacity (Btu/hr) 17244 19875 22754 25903 29344 33098 37189 41637 46466 51696
Power (kW) 2.64 2.79 2.93 3.06 3.18 3.3 3.4 3.49 3.58 3.66
EER (BTU/WATT-HR) 6.54 7.13 7.76 8.46 9.22 10.04 10.94 11.92 12.98 14.14
Current (AMPS) 5.99 6.36 6.71 7.03 7.31 7.56 7.78 7.95 8.09 8.18
130 Capacity (Btu/hr) 12716 14802 17078 19566 22289 25267 28524 32080 35959 40180
Power (kW) 2.66 2.87 3.07 3.26 3.44 3.62 3.78 3.94 4.09 4.23
EER (BTU/WATT-HR) 4.78 5.16 5.56 6 6.47 6.99 7.55 8.15 8.8 9.5
Current (AMPS) 6.07 6.57 7.03 7.46 7.86 8.22 8.54 8.82 9.05 9.24

 

 

06DM313   R404A/R507 Refrigerants

Physical Data
Model Nominal HP Displ. CFM No. of Cylinders Suction Line Size (in) Discharge Line Size (in) Shipping Weight (lbs) Oil Charge (pints)
06DM313 5 13 4 7/8 5/8 235 4 1/2

 

Available Voltages
208/230-3-60
460-3-60
575-3-60

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 10

 

Tabular Data Summary – Fixed RGT = 65°F Subcooling = 0°F Voltage: 460-3-60Hz
Saturated Condensing Temperature (F) 5 10 15 20 25 30 35 40 45 50
90 Capacity (Btu/hr) 33740 38970 44659 50841 57548 64814 72671 81152 90290 100118
Power (kW) 3.36 3.54 3.7 3.85 3.99 4.12 4.23 4.32 4.41 4.49
EER (BTU/WATT-HR) 10.03 11.01 12.05 13.19 14.42 15.75 17.2 18.77 20.47 22.32
Current (AMPS) 5.37 5.57 5.76 5.94 6.11 6.27 6.42 6.56 6.69 6.82
110 Capacity (Btu/hr) 25668 30154 35017 40291 46008 52201 58904 66149 73970 82399
Power (kW) 3.57 3.84 4.08 4.31 4.53 4.73 4.91 5.08 5.24 5.38
EER (BTU/WATT-HR) 7.18 7.86 8.58 9.34 10.16 11.04 11.99 13.02 14.13 15.33
Current (AMPS) 5.61 5.92 6.22 6.52 6.82 7.12 7.41 7.71 8 8.29
130 Capacity (Btu/hr) 17435 21076 25012 29273 33893 38905 44342 50236 56620 63527
Power (kW) 3.56 3.93 4.28 4.61 4.92 5.21 5.49 5.75 5.99 6.21
EER (BTU/WATT-HR) 4.89 5.36 5.85 6.35 6.89 7.46 8.08 8.74 9.45 10.22
Current (AMPS) 5.59 6.05 6.51 6.98 7.45 7.93 8.41 8.9 9.4 9.9

 

 

 

06DRM316   R404A/R507 Refrigerants

Physical Data
Model Nominal HP Displ. CFM No. of Cylinders Suction Line Size (in) Discharge Line Size (in) Shipping Weight (lbs) Oil Charge (pints)
06DM316 5 15.9 4 1 1/8 5/8 235 4 1/2

 

Available Voltages
208/230-3-60
460-3-60
575-3-60

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 11

 

Tabular Data Summary – Fixed RGT = 65°F Subcooling = 0°F Voltage: 460-3-60Hz
Saturated Condensing Temperature (F) 5 10 15 20 25
90 Capacity (Btu/hr) 43564 50217 57564 65662 74568
Power (kW) 4.58 4.78 4.95 5.1 5.23
EER (BTU/WATT-HR) 9.51 10.51 11.62 12.86 14.26
Current (AMPS) 6.91 7.16 7.39 7.58 7.75
110 Capacity (Btu/hr) 33855 39329 45353 51982 59272
Power (kW) 4.89 5.21 5.5 5.75 5.98
EER (BTU/WATT-HR) 6.93 7.56 8.25 9.03 9.91
Current (AMPS) 7.35 7.76 8.14 8.51 8.85
130 Capacity (Btu/hr) 24418 28694 33372 38505 44152
Power (kW) 4.88 5.33 5.75 6.13 6.46
EER (BTU/WATT-HR) 5 5.38 5.81 6.29 6.83
Current (AMPS) 7.26 7.89 8.51 9.11 9.69

 

 

CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 12CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 13CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 14CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 15CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 16CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 17CARLYLE COMPRESSOR 06DR R404A 220V 380V 460 575V Power Supply compressor 18