xProduct Details
Standard Motor | 380V/3/50Hz-460/3/60Hz | Refrigerant | R22/R404A |
---|---|---|---|
Quality Assurance | A Year | Nominal HP | Describe |
Highlight | R22 Screw Refrigeration Compressor,Screw Refrigeration Compressor 380V,145m3/H Displacement Screw Refrigeration Compressor |
Product Description
Model | SLG | 100-35 | 120-40 | 140-50 | 190-65 | 210-70 | 230-80 | 290-100 | 320-110 | 350-120 | 370-130 | 420-145 | 470-160 | 520-180 | 570-195 | 640-210 | ||||||||||||||||||||||||||||||||||||||||||||||||||
Displacement 50Hz | m3/h | 102 | 128 | 145 | 188 | 205 | 235 | 293 | 322 | 354 | 368 | 416 | 469 | 520 | 572 | 641 | ||||||||||||||||||||||||||||||||||||||||||||||||||
Nominal Motor Power | Hp/kW | 40/30 | 40/30 | 50/37 | 70/52 | 70/52 | 80/60 | 100/75 | 115/83 | 120/89 | 130/98 | 145/108 | 160/120 | 180/135 | 195/146 | 210/157 | ||||||||||||||||||||||||||||||||||||||||||||||||||
Weight | Kg | 245 | 245 | 255 | 405 | 410 | 420 | 535 | 540 | 545 | 665 | 675 | 710 | 1030 | 1050 | 1050 | ||||||||||||||||||||||||||||||||||||||||||||||||||
Discharge line, internal | mm | 45 | 45 | 45 | 57 | 57 | 57 | 57 | 57 | 57 | 76 | 76 | 76 | 76 | 76 | 76 | ||||||||||||||||||||||||||||||||||||||||||||||||||
Suction line, internal | mm | 57 | 57 | 57 | 76 | 76 | 76 | 89 | 89 | 89 | 89 | 89 | 89 | 108 | 108 | 108 | ||||||||||||||||||||||||||||||||||||||||||||||||||
Energy regulation | 40%,70%,100% | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Protection module | INT 69 RCY | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Standard motor | 380V/3/50Hz-460/3/60Hz | |||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
Starting current | A | 134 | 134 | 139 | 193 | 193 | 298 | 338 | 354 | 366 | 453 | 453 | 543 | 595 | 678 | 767 | ||||||||||||||||||||||||||||||||||||||||||||||||||
A | 134 | 134 | 182 | 139 | 193 | 338 | 318 | 318 | 354 | 374 | 453 | 543 | 595 | 595 | 595 | |||||||||||||||||||||||||||||||||||||||||||||||||||
Maximum working current | A | 56 | 60 | 78 | 104 | 109 | 126 | 158 | 175 | 187 | 206 | 228 | 253 | 284 | 308 | 331 |
PERFORMANCES SLG R22
SLG 100-35(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 42.5 | 17.4 | 40.1 | 19.2 | 37.4 | 21.6 | 34.3 | 21.9 | 30.8 | 24.3 | — | — | ||||||||||||||||||||
-15 | 52.2 | 17.6 | 49.2 | 19.2 | 45.9 | 21.6 | 42.2 | 22.4 | 38.2 | 24.9 | — | — | ||||||||||||||||||||
-10 | 63.5 | 17.7 | 60.0 | 19.4 | 56.1 | 21.7 | 51.9 | 22.9 | 47.5 | 25.4 | 38.2 | 31.1 | ||||||||||||||||||||
-5 | 76.3 | 18.0 | 72.3 | 19.8 | 68.0 | 21.8 | 63.4 | 23.4 | 58.8 | 25.9 | 48.7 | 31.8 | ||||||||||||||||||||
0 | 90.7 | 18.4 | 86.3 | 20.1 | 81.6 | 22.1 | 76.8 | 23.9 | 71.8 | 26.5 | 61.5 | 32.6 | ||||||||||||||||||||
5 | 106.5 | 18.7 | 101.8 | 20.4 | 96.9 | 22.6 | 91.9 | 24.5 | 86.7 | 27.1 | — | — | ||||||||||||||||||||
10 | — | — | 118.9 | 21.1 | 113.9 | 23.2 | 108.8 | 25.0 | 103.5 | 27.8 | — | — |
SLG 100 -35(R22)ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 49.0 | 18.7 | 47.8 | 20.9 | 46.1 | 23.8 | 44.0 | 25.1 | 41.2 | 27.8 | — | — | ||||||||||||||||||||
-15 | 58.7 | 18.9 | 57.1 | 21.0 | 55.0 | 23.9 | 52.5 | 25.2 | 49.4 | 27.9 | — | — | ||||||||||||||||||||
-10 | 69.4 | 19.1 | 67.5 | 21.0 | 65.3 | 23.9 | 62.6 | 25.3 | 59.4 | 28.0 | 52.0 | 34.2 | ||||||||||||||||||||
-5 | 81.2 | 19.1 | 79.3 | 21.2 | 76.9 | 24.0 | 74.2 | 25.6 | 71.1 | 28.1 | 64.0 | 34.6 | ||||||||||||||||||||
0 | 94.0 | 19.2 | 92.0 | 21.3 | 89.6 | 23.9 | 87.1 | 25.8 | 84.3 | 28.2 | 77.8 | 34.8 | ||||||||||||||||||||
5 | 107.4 | 19.3 | 109.6 | 21.5 | 106.6 | 24.1 | 101.2 | 26.0 | 98.6 | 28.4 | — | — | ||||||||||||||||||||
10 | — | — | 126.7 | 22.1 | 124.7 | 24.3 | 120.6 | 26.6 | 114.1 | 28.6 | — | — |
SLG 230 -80(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 99.8 | 40.9 | 94.2 | 45.1 | 87.8 | 50.8 | 80.5 | 51.5 | 72.5 | 57.2 | — | — | ||||||||||||||||||||
-15 | 122.8 | 41.4 | 115.7 | 45.1 | 107.8 | 50.8 | 99.2 | 52.5 | 89.9 | 58.4 | — | — | ||||||||||||||||||||
-10 | 149.3 | 41.6 | 140.9 | 45.6 | 131.7 | 51.0 | 122.0 | 53.8 | 111.7 | 59.6 | 89.7 | 73.2 | ||||||||||||||||||||
-5 | 179.4 | 42.3 | 169.8 | 46.5 | 159.8 | 51.2 | 149.1 | 55.0 | 138.1 | 60.8 | 114.5 | 74.8 | ||||||||||||||||||||
0 | 213.2 | 43.2 | 202.7 | 47.2 | 191.7 | 51.9 | 180.5 | 56.2 | 168.7 | 62.2 | 144.4 | 76.6 | ||||||||||||||||||||
5 | 250.4 | 44.1 | 239.2 | 47.9 | 227.8 | 53.1 | 216.0 | 57.6 | 203.9 | 63.7 | — | — | ||||||||||||||||||||
10 | — | — | 279.5 | 49.5 | 267.6 | 54.5 | 255.6 | 58.8 | 243.3 | 65.3 | — | — |
SLG 230 -80 (R22) ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 115.1 | 43.9 | 112.2 | 49.1 | 108.4 | 55.9 | 103.3 | 59.0 | 96.9 | 65.3 | — | — | ||||||||||||||||||||
-15 | 137.9 | 44.4 | 134.1 | 49.4 | 129.2 | 56.0 | 123.4 | 59.2 | 116.1 | 65.6 | — | — | ||||||||||||||||||||
-10 | 163.2 | 44.9 | 158.7 | 49.4 | 153.4 | 56.2 | 147.2 | 59.5 | 139.6 | 65.8 | 122.2 | 80.4 | ||||||||||||||||||||
-5 | 190.9 | 44.9 | 186.2 | 49.8 | 180.7 | 56.3 | 174.3 | 60.2 | 167.2 | 66.0 | 150.4 | 81.3 | ||||||||||||||||||||
0 | 220.8 | 45.1 | 216.1 | 50.1 | 210.6 | 56.1 | 204.7 | 60.6 | 198.0 | 66.3 | 182.9 | 81.8 | ||||||||||||||||||||
5 | 252.3 | 45.4 | 257.6 | 50.5 | 250.5 | 56.6 | 237.7 | 61.1 | 231.8 | 66.7 | — | — | ||||||||||||||||||||
10 | — | — | 297.7 | 51.9 | 293.0 | 57.1 | 283.4 | 62.5 | 268.2 | 67.2 | — | — |
SLG120-40(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 51.8 | 21.2 | 48.9 | 23.4 | 45.6 | 26.4 | 41.8 | 26.8 | 37.6 | 29.7 | — | — | ||||||||||||||||||||
-15 | 63.7 | 21.5 | 60.0 | 23.4 | 56.0 | 26.4 | 51.5 | 27.3 | 46.7 | 30.3 | — | — | ||||||||||||||||||||
-10 | 77.5 | 21.6 | 73.1 | 23.7 | 68.4 | 26.5 | 63.3 | 27.9 | 58.0 | 31.0 | 46.6 | 38.0 | ||||||||||||||||||||
-5 | 93.1 | 22.0 | 88.2 | 24.2 | 82.9 | 26.6 | 77.4 | 28.5 | 71.7 | 31.6 | 59.5 | 38.8 | ||||||||||||||||||||
0 | 110.7 | 22.4 | 105.2 | 24.5 | 99.5 | 27.0 | 93.7 | 29.2 | 87.6 | 32.3 | 75.0 | 39.8 | ||||||||||||||||||||
5 | 130.0 | 22.9 | 124.2 | 24.9 | 118.2 | 27.6 | 112.1 | 29.9 | 105.8 | 33.0 | — | — | ||||||||||||||||||||
10 | — | — | 145.1 | 25.7 | 138.9 | 28.3 | 132.7 | 30.5 | 126.3 | 33.9 | — | — |
SLG 120-40(R22)ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 59.8 | 22.8 | 58.3 | 25.5 | 56.3 | 29.0 | 53.6 | 30.6 | 50.3 | 33.9 | — | — | ||||||||||||||||||||
-15 | 71.6 | 23.1 | 69.6 | 25.6 | 67.1 | 29.1 | 64.0 | 30.7 | 60.3 | 34.0 | — | — | ||||||||||||||||||||
-10 | 84.7 | 23.3 | 82.4 | 25.6 | 79.6 | 29.2 | 76.4 | 30.9 | 72.5 | 34.2 | 63.4 | 41.7 | ||||||||||||||||||||
-5 | 99.1 | 23.3 | 96.7 | 25.9 | 93.8 | 29.2 | 90.5 | 31.2 | 86.8 | 34.3 | 78.1 | 42.2 | ||||||||||||||||||||
0 | 114.6 | 23.4 | 112.2 | 26.0 | 109.3 | 29.1 | 106.3 | 31.5 | 102.8 | 34.4 | 95.0 | 42.5 | ||||||||||||||||||||
5 | 131.0 | 23.5 | 133.7 | 26.2 | 130.1 | 29.4 | 123.4 | 31.7 | 120.3 | 34.6 | — | — | ||||||||||||||||||||
10 | — | — | 154.6 | 27.0 | 152.1 | 29.6 | 147.1 | 32.5 | 139.3 | 34.9 | — | — |
SLG 290-100(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 125.3 | 51.3 | 118.2 | 56.6 | 110.2 | 63.7 | 101.1 | 64.7 | 91.0 | 71.8 | — | — | ||||||||||||||||||||
-15 | 154.1 | 51.9 | 145.2 | 56.6 | 135.3 | 63.7 | 124.5 | 66.0 | 112.8 | 73.3 | — | — | ||||||||||||||||||||
-10 | 187.4 | 52.2 | 176.9 | 57.2 | 165.4 | 64.0 | 153.2 | 67.5 | 140.3 | 74.8 | 112.6 | 91.8 | ||||||||||||||||||||
-5 | 225.2 | 53.1 | 213.2 | 58.4 | 200.5 | 64.3 | 187.2 | 69.0 | 173.3 | 76.4 | 143.8 | 93.9 | ||||||||||||||||||||
0 | 267.6 | 54.3 | 254.5 | 59.3 | 240.7 | 65.2 | 226.6 | 70.5 | 211.8 | 78.1 | 181.3 | 96.2 | ||||||||||||||||||||
5 | 314.3 | 55.3 | 300.2 | 60.1 | 285.9 | 66.7 | 271.1 | 72.3 | 255.9 | 79.9 | — | — | ||||||||||||||||||||
10 | — | — | 350.9 | 62.2 | 335.9 | 68.4 | 320.9 | 73.8 | 305.4 | 81.9 | — | — |
SLG 290-100(R22) ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 144.5 | 55.2 | 140.9 | 61.7 | 136.1 | 70.2 | 129.7 | 74.0 | 121.6 | 82.0 | — | — | ||||||||||||||||||||
-15 | 173.2 | 55.8 | 168.4 | 62.0 | 162.2 | 70.4 | 154.8 | 74.3 | 145.8 | 82.3 | — | — | ||||||||||||||||||||
-10 | 204.9 | 56.3 | 199.2 | 62.0 | 192.6 | 70.5 | 184.7 | 74.6 | 175.3 | 82.6 | 153.4 | 100.9 | ||||||||||||||||||||
-5 | 239.6 | 56.3 | 233.8 | 62.5 | 226.9 | 70.7 | 218.8 | 75.5 | 209.9 | 82.9 | 188.8 | 102.1 | ||||||||||||||||||||
0 | 277.2 | 56.6 | 271.3 | 62.8 | 264.3 | 70.4 | 257.0 | 76.1 | 248.5 | 83.2 | 229.6 | 102.7 | ||||||||||||||||||||
5 | 316.8 | 56.9 | 323.3 | 63.4 | 314.5 | 71.1 | 298.4 | 76.7 | 291.0 | 83.8 | — | — | ||||||||||||||||||||
10 | — | — | 373.8 | 65.2 | 367.9 | 71.7 | 355.8 | 78.5 | 336.7 | 84.4 | — | — |
SLG 140-50(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 60.3 | 24.7 | 56.9 | 27.3 | 53.1 | 30.7 | 48.7 | 31.1 | 43.8 | 34.6 | — | — | ||||||||||||||||||||
-15 | 74.2 | 25.0 | 69.9 | 27.3 | 65.1 | 30.7 | 60.0 | 31.8 | 54.3 | 35.3 | — | — | ||||||||||||||||||||
-10 | 90.2 | 25.1 | 85.1 | 27.5 | 79.6 | 30.8 | 73.7 | 32.5 | 67.5 | 36.0 | 54.2 | 44.2 | ||||||||||||||||||||
-5 | 108.4 | 25.6 | 102.6 | 28.1 | 96.5 | 31.0 | 90.1 | 33.2 | 83.4 | 36.8 | 69.2 | 45.2 | ||||||||||||||||||||
0 | 128.8 | 26.1 | 122.5 | 28.5 | 115.8 | 31.4 | 109.1 | 33.9 | 102.0 | 37.6 | 87.3 | 46.3 | ||||||||||||||||||||
5 | 151.3 | 26.6 | 144.5 | 28.9 | 137.6 | 32.1 | 130.5 | 34.8 | 123.2 | 38.5 | — | — | ||||||||||||||||||||
10 | — | — | 168.9 | 29.9 | 161.7 | 32.9 | 154.5 | 35.5 | 147.0 | 39.4 | — | — |
SLG 140-50 (R22) ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 69.6 | 26.6 | 67.8 | 29.7 | 65.5 | 33.8 | 62.4 | 35.6 | 58.5 | 39.5 | — | — | ||||||||||||||||||||
-15 | 83.4 | 26.8 | 81.0 | 29.8 | 78.1 | 33.9 | 74.5 | 35.8 | 70.2 | 39.6 | — | — | ||||||||||||||||||||
-10 | 98.6 | 27.1 | 95.9 | 29.8 | 92.7 | 33.9 | 88.9 | 35.9 | 84.4 | 39.8 | 73.8 | 48.6 | ||||||||||||||||||||
-5 | 115.3 | 27.1 | 112.5 | 30.1 | 109.2 | 34.0 | 105.3 | 36.4 | 101.0 | 39.9 | 90.9 | 49.1 | ||||||||||||||||||||
0 | 133.4 | 27.3 | 130.6 | 30.2 | 127.2 | 33.9 | 123.7 | 36.6 | 119.6 | 40.0 | 110.5 | 49.4 | ||||||||||||||||||||
5 | 152.5 | 27.4 | 155.6 | 30.5 | 151.4 | 34.2 | 143.7 | 36.9 | 140.1 | 40.3 | — | — | ||||||||||||||||||||
10 | — | — | 179.9 | 31.4 | 177.1 | 34.5 | 171.3 | 37.8 | 162.1 | 40.6 | — | — |
SLG 320-110(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 138.4 | 56.7 | 130.6 | 62.6 | 121.8 | 70.4 | 111.7 | 71.5 | 100.6 | 79.3 | — | — | ||||||||||||||||||||
-15 | 170.3 | 57.4 | 160.4 | 62.6 | 149.6 | 70.4 | 137.6 | 72.9 | 124.7 | 81.0 | — | — | ||||||||||||||||||||
-10 | 207.1 | 57.7 | 195.4 | 63.2 | 182.7 | 70.7 | 169.3 | 74.6 | 155.0 | 82.7 | 124.4 | 101.5 | ||||||||||||||||||||
-5 | 248.8 | 58.7 | 235.6 | 64.5 | 221.6 | 71.1 | 206.8 | 76.3 | 191.5 | 84.4 | 158.9 | 103.7 | ||||||||||||||||||||
0 | 295.7 | 60.0 | 281.2 | 65.5 | 265.9 | 72.0 | 250.4 | 77.9 | 234.1 | 86.4 | 200.4 | 106.3 | ||||||||||||||||||||
5 | 347.3 | 61.1 | 331.8 | 66.4 | 316.0 | 73.7 | 299.6 | 79.9 | 282.8 | 88.3 | — | — | ||||||||||||||||||||
10 | — | — | 387.8 | 68.7 | 371.2 | 75.6 | 354.6 | 81.5 | 337.5 | 90.6 | — | — |
SLG 320 -110 (R22) ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 159.7 | 61.0 | 155.7 | 68.1 | 150.4 | 77.6 | 143.3 | 81.8 | 134.4 | 90.6 | — | — | ||||||||||||||||||||
-15 | 191.4 | 61.6 | 186.1 | 68.5 | 179.2 | 77.8 | 171.1 | 82.2 | 161.1 | 91.0 | — | — | ||||||||||||||||||||
-10 | 226.4 | 62.3 | 220.2 | 68.5 | 212.8 | 77.9 | 204.2 | 82.5 | 193.7 | 91.3 | 169.5 | 111.5 | ||||||||||||||||||||
-5 | 264.8 | 62.3 | 258.4 | 69.1 | 250.7 | 78.1 | 241.8 | 83.5 | 231.9 | 91.6 | 208.6 | 112.8 | ||||||||||||||||||||
0 | 306.3 | 62.6 | 299.8 | 69.4 | 292.1 | 77.8 | 284.0 | 84.1 | 274.7 | 91.9 | 253.8 | 113.4 | ||||||||||||||||||||
5 | 350.1 | 62.9 | 357.3 | 70.1 | 347.5 | 78.6 | 329.8 | 84.8 | 321.6 | 92.6 | — | — | ||||||||||||||||||||
10 | — | — | 413.0 | 72.0 | 406.5 | 79.2 | 393.2 | 86.7 | 372.1 | 93.2 | — | — |
SLG 190-65(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 84.1 | 34.1 | 79.3 | 37.6 | 74.0 | 42.3 | 67.9 | 43.0 | 61.1 | 47.7 | — | — | ||||||||||||||||||||
-15 | 103.4 | 34.5 | 97.4 | 37.6 | 90.8 | 42.3 | 83.6 | 43.8 | 75.7 | 48.7 | — | — | ||||||||||||||||||||
-10 | 125.8 | 34.7 | 118.7 | 38.0 | 111.0 | 42.5 | 102.8 | 44.8 | 94.1 | 49.7 | 75.6 | 61.0 | ||||||||||||||||||||
-5 | 151.1 | 35.3 | 143.1 | 38.8 | 134.6 | 42.7 | 125.6 | 45.8 | 116.3 | 50.7 | 96.5 | 62.4 | ||||||||||||||||||||
0 | 179.6 | 36.1 | 170.8 | 39.4 | 161.5 | 43.3 | 152.1 | 46.9 | 142.2 | 51.9 | 121.7 | 63.9 | ||||||||||||||||||||
5 | 211.0 | 36.7 | 201.5 | 39.9 | 191.9 | 44.3 | 182.0 | 48.0 | 171.8 | 53.1 | — | — | ||||||||||||||||||||
10 | — | — | 235.5 | 41.3 | 225.4 | 45.5 | 215.4 | 49.0 | 205.0 | 54.4 | — | — |
SLG 190-65 (R22) ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 94.1 | 35.5 | 91.7 | 39.7 | 88.6 | 45.2 | 84.4 | 47.7 | 79.1 | 52.8 | — | — | ||||||||||||||||||||
-15 | 112.7 | 35.9 | 109.6 | 39.9 | 105.5 | 45.3 | 100.8 | 47.9 | 94.9 | 53.0 | — | — | ||||||||||||||||||||
-10 | 133.3 | 36.3 | 129.7 | 39.9 | 125.4 | 45.4 | 120.2 | 48.1 | 114.1 | 53.2 | 99.8 | 65.0 | ||||||||||||||||||||
-5 | 155.9 | 36.3 | 152.2 | 40.3 | 147.7 | 45.5 | 142.4 | 48.6 | 136.6 | 53.4 | 122.9 | 65.7 | ||||||||||||||||||||
0 | 180.4 | 36.5 | 176.6 | 40.5 | 172.0 | 45.4 | 167.3 | 49.0 | 161.8 | 53.6 | 149.5 | 66.1 | ||||||||||||||||||||
5 | 206.2 | 36.7 | 210.4 | 40.9 | 204.7 | 45.8 | 194.2 | 49.4 | 189.4 | 54.0 | — | — | ||||||||||||||||||||
10 | — | — | 243.3 | 42.0 | 239.4 | 46.2 | 231.6 | 50.5 | 219.1 | 54.3 | — | — |
SLG 350-120(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 152.8 | 62.6 | 144.3 | 69.1 | 134.5 | 77.8 | 123.4 | 78.9 | 111.1 | 87.6 | — | — | ||||||||||||||||||||
-15 | 188.1 | 63.4 | 177.2 | 69.1 | 165.2 | 77.8 | 152.0 | 80.5 | 137.7 | 89.5 | — | — | ||||||||||||||||||||
-10 | 228.7 | 63.7 | 215.8 | 69.8 | 201.8 | 78.1 | 186.9 | 82.4 | 171.2 | 91.3 | 137.4 | 112.1 | ||||||||||||||||||||
-5 | 274.8 | 64.8 | 260.2 | 71.3 | 244.7 | 78.5 | 228.4 | 84.2 | 211.5 | 93.2 | 175.5 | 114.6 | ||||||||||||||||||||
0 | 326.6 | 66.2 | 310.6 | 72.4 | 293.7 | 79.6 | 276.5 | 86.1 | 258.5 | 95.4 | 221.3 | 117.3 | ||||||||||||||||||||
5 | 383.6 | 67.5 | 366.4 | 73.4 | 348.9 | 81.4 | 330.9 | 88.2 | 312.3 | 97.5 | — | — | ||||||||||||||||||||
10 | — | — | 428.2 | 75.9 | 409.9 | 83.5 | 391.6 | 90.0 | 372.7 | 100.0 | — | — |
SLG 350-120 (R22) ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 176.4 | 67.3 | 171.9 | 75.2 | 166.1 | 85.7 | 158.3 | 90.4 | 148.4 | 100.1 | — | — | ||||||||||||||||||||
-15 | 211.3 | 68.0 | 205.5 | 75.6 | 197.9 | 85.9 | 189.0 | 90.7 | 177.9 | 100.4 | — | — | ||||||||||||||||||||
-10 | 250.0 | 68.8 | 243.2 | 75.6 | 235.0 | 86.0 | 225.4 | 91.1 | 213.9 | 100.8 | 187.1 | 123.1 | ||||||||||||||||||||
-5 | 292.4 | 68.8 | 285.3 | 76.3 | 276.9 | 86.2 | 267.1 | 92.2 | 256.1 | 101.2 | 230.4 | 124.6 | ||||||||||||||||||||
0 | 338.3 | 69.1 | 331.1 | 76.7 | 322.6 | 85.9 | 313.6 | 92.9 | 303.3 | 101.5 | 280.2 | 125.3 | ||||||||||||||||||||
5 | 386.6 | 69.5 | 394.6 | 77.4 | 383.8 | 86.8 | 364.2 | 93.6 | 355.1 | 102.2 | — | — | ||||||||||||||||||||
10 | — | — | 456.1 | 79.6 | 448.9 | 87.5 | 434.2 | 95.8 | 410.9 | 103.0 | — | — |
SLG 210-70(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 89.2 | 36.5 | 84.2 | 40.3 | 78.5 | 45.4 | 72.0 | 46.1 | 64.8 | 51.1 | — | — | ||||||||||||||||||||
-15 | 109.7 | 37.0 | 103.4 | 40.3 | 96.3 | 45.4 | 88.7 | 47.0 | 80.3 | 52.2 | — | — | ||||||||||||||||||||
-10 | 133.4 | 37.2 | 125.9 | 40.7 | 117.7 | 45.6 | 109.0 | 48.0 | 99.8 | 53.3 | 80.1 | 65.4 | ||||||||||||||||||||
-5 | 160.3 | 37.8 | 151.8 | 41.6 | 142.8 | 45.8 | 133.2 | 49.1 | 123.4 | 54.4 | 102.4 | 66.8 | ||||||||||||||||||||
0 | 190.5 | 38.6 | 181.2 | 42.2 | 171.3 | 46.4 | 161.3 | 50.2 | 150.8 | 55.6 | 129.1 | 68.4 | ||||||||||||||||||||
5 | 223.7 | 39.4 | 213.7 | 42.8 | 203.5 | 47.5 | 193.0 | 51.5 | 182.2 | 56.9 | — | — | ||||||||||||||||||||
10 | — | — | 249.8 | 44.2 | 239.1 | 48.7 | 228.4 | 52.5 | 217.4 | 58.3 | — | — |
SLG 210 -70 (R22) ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 102.9 | 39.3 | 100.3 | 43.9 | 96.9 | 50.0 | 92.3 | 52.7 | 86.5 | 58.4 | — | — | ||||||||||||||||||||
-15 | 123.3 | 39.7 | 119.9 | 44.1 | 115.4 | 50.1 | 110.2 | 52.9 | 103.8 | 58.6 | — | — | ||||||||||||||||||||
-10 | 145.8 | 40.1 | 141.8 | 44.1 | 137.1 | 50.2 | 131.5 | 53.1 | 124.8 | 58.8 | 109.2 | 71.8 | ||||||||||||||||||||
-5 | 170.6 | 40.1 | 166.4 | 44.5 | 161.5 | 50.3 | 155.8 | 53.8 | 149.4 | 59.0 | 134.4 | 72.7 | ||||||||||||||||||||
0 | 197.3 | 40.3 | 193.1 | 44.7 | 188.2 | 50.1 | 182.9 | 54.2 | 176.9 | 59.2 | 163.5 | 73.1 | ||||||||||||||||||||
5 | 225.5 | 40.5 | 230.2 | 45.2 | 223.9 | 50.6 | 212.4 | 54.6 | 207.2 | 59.6 | — | — | ||||||||||||||||||||
10 | — | — | 266.1 | 46.4 | 261.9 | 51.0 | 253.3 | 55.9 | 239.7 | 60.1 | — | — |
SLG 370-130(R22) | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 159.2 | 65.3 | 150.3 | 72.0 | 140.1 | 81.0 | 128.5 | 82.2 | 115.7 | 91.3 | — | — | ||||||||||||||||||||
-15 | 195.9 | 66.0 | 184.6 | 72.0 | 172.0 | 81.0 | 158.3 | 83.9 | 143.4 | 93.2 | — | — | ||||||||||||||||||||
-10 | 238.2 | 66.4 | 224.8 | 72.8 | 210.2 | 81.4 | 194.7 | 85.8 | 178.3 | 95.1 | 143.1 | 116.7 | ||||||||||||||||||||
-5 | 286.2 | 67.5 | 271.0 | 74.3 | 254.9 | 81.8 | 237.9 | 87.7 | 220.3 | 97.1 | 182.8 | 119.3 | ||||||||||||||||||||
0 | 340.2 | 69.0 | 323.5 | 75.4 | 305.9 | 82.9 | 288.0 | 89.7 | 269.2 | 99.3 | 230.5 | 122.2 | ||||||||||||||||||||
5 | 399.5 | 70.3 | 381.6 | 76.4 | 363.5 | 84.8 | 344.7 | 91.9 | 325.3 | 101.6 | — | — | ||||||||||||||||||||
10 | — | — | 446.0 | 79.0 | 427.0 | 87.0 | 407.9 | 93.8 | 388.2 | 104.2 | — | — |
SLG 370-130 (R22) ECO | ||||||||||||||||||||||||||||||||
Tc | 30 | 35 | 40 | 45 | 50 | 60 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 183.7 | 70.1 | 179.1 | 78.4 | 173.0 | 89.3 | 164.9 | 94.1 | 154.5 | 104.3 | — | — | ||||||||||||||||||||
-15 | 220.1 | 70.9 | 214.0 | 78.8 | 206.1 | 89.4 | 196.8 | 94.5 | 185.3 | 104.6 | — | — | ||||||||||||||||||||
-10 | 260.4 | 71.6 | 253.3 | 78.8 | 244.8 | 89.6 | 234.8 | 94.9 | 222.8 | 105.0 | 194.9 | 128.3 | ||||||||||||||||||||
-5 | 304.6 | 71.6 | 297.2 | 79.5 | 288.4 | 89.8 | 278.2 | 96.0 | 266.8 | 105.4 | 240.0 | 129.8 | ||||||||||||||||||||
0 | 352.4 | 72.0 | 344.9 | 79.9 | 336.0 | 89.5 | 326.7 | 96.8 | 315.9 | 105.8 | 291.9 | 130.5 | ||||||||||||||||||||
5 | 402.7 | 72.4 | 411.0 | 80.6 | 399.8 | 90.4 | 379.4 | 97.5 | 369.9 | 106.5 | — | — | ||||||||||||||||||||
10 | — | — | 475.1 | 82.9 | 467.6 | 91.1 | 452.3 | 99.8 | 428.0 | 107.3 | — | — |
PERFORMANCES SLG R404A
SLG 100-35(R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 49.2 | 17.4 | 43.5 | 20.4 | 41.2 | 22.6 | 37.4 | 24.9 | 32.6 | 27.8 | 28.0 | 30.5 | ||||||||||||||||||||
-15 | 61.5 | 17.8 | 53.5 | 20.6 | 51.8 | 23.1 | 46.2 | 25.3 | 40.2 | 28.6 | 35.8 | 31.1 | ||||||||||||||||||||
-10 | 76.0 | 18.2 | 66.8 | 21.2 | 62.5 | 23.6 | 56.8 | 25.8 | 51.2 | 29.2 | 45.7 | 31.9 | ||||||||||||||||||||
-5 | 90.5 | 18.6 | 80.7 | 21.9 | 75.3 | 24.2 | 69.3 | 26.5 | 62.8 | 29.7 | 55.6 | 32.5 | ||||||||||||||||||||
0 | — | — | 96.9 | 22.7 | 91.4 | 24.8 | 84.2 | 27.0 | 76.7 | 30.2 | 71.0 | 33.2 | ||||||||||||||||||||
5 | — | — | 116.5 | 23.5 | 107.2 | 25.3 | 100.5 | 27.8 | 92.6 | 30.5 | 83.1 | 33.7 |
SLG 100-35 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 60.4 | 18.6 | 59.0 | 22.7 | 56.7 | 25.4 | 53.5 | 28.6 | 48.9 | 31.5 | 47.6 | 36.2 | ||||||||||||||||||||
-15 | 72.2 | 18.8 | 69.5 | 22.9 | 66.7 | 25.6 | 62.9 | 28.8 | 58.2 | 31.7 | 57.2 | 36.5 | ||||||||||||||||||||
-10 | 85.3 | 19.1 | 81.3 | 23.2 | 78.1 | 25.7 | 73.9 | 29.0 | 68.9 | 31.8 | 67.4 | 36.6 | ||||||||||||||||||||
-5 | 99.5 | 19.2 | 94.3 | 23.5 | 90.8 | 25.9 | 86.4 | 29.2 | 81.1 | 32.2 | 77.2 | 36.8 | ||||||||||||||||||||
0 | — | — | 108.5 | 23.7 | 104.5 | 26.1 | 100.3 | 29.3 | 94.6 | 32.5 | 90.6 | 36.7 | ||||||||||||||||||||
5 | — | — | 123.3 | 23.8 | 119.1 | 26.2 | 114.7 | 29.3 | 109.1 | 32.6 | 103.2 | 36.9 |
SLG 230-80(R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 116.6 | 39.6 | 103.1 | 46.4 | 97.6 | 51.4 | 88.6 | 56.6 | 77.3 | 63.2 | 66.3 | 69.4 | ||||||||||||||||||||
-15 | 145.8 | 40.5 | 126.8 | 46.8 | 122.8 | 52.5 | 109.5 | 57.5 | 95.3 | 65.0 | 84.9 | 70.7 | ||||||||||||||||||||
-10 | 180.1 | 41.4 | 158.3 | 48.2 | 148.1 | 53.7 | 134.6 | 58.7 | 121.3 | 66.4 | 108.3 | 72.5 | ||||||||||||||||||||
-5 | 214.5 | 42.3 | 191.3 | 49.8 | 178.5 | 55.0 | 164.2 | 60.3 | 148.8 | 67.5 | 131.8 | 73.9 | ||||||||||||||||||||
0 | — | — | 229.7 | 51.6 | 216.6 | 56.4 | 199.6 | 61.4 | 181.8 | 68.7 | 168.4 | 75.5 | ||||||||||||||||||||
5 | — | — | 276.1 | 53.4 | 254.1 | 57.5 | 238.2 | 63.2 | 219.5 | 69.4 | 196.9 | 76.6 |
SLG 230-80 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 143.2 | 42.3 | 139.7 | 51.6 | 134.4 | 57.8 | 126.7 | 65.0 | 116.0 | 71.6 | 112.8 | 82.3 | ||||||||||||||||||||
-15 | 171.1 | 42.8 | 164.6 | 52.1 | 158.0 | 58.2 | 149.2 | 65.5 | 137.9 | 72.1 | 135.6 | 83.0 | ||||||||||||||||||||
-10 | 202.2 | 43.4 | 192.7 | 52.8 | 185.2 | 58.4 | 175.2 | 66.0 | 163.3 | 72.3 | 159.7 | 83.2 | ||||||||||||||||||||
-5 | 235.8 | 43.7 | 223.5 | 53.4 | 215.2 | 58.9 | 204.8 | 66.4 | 192.2 | 73.2 | 183.0 | 83.7 | ||||||||||||||||||||
0 | — | — | 257.1 | 53.9 | 247.5 | 59.4 | 237.7 | 66.6 | 224.1 | 73.9 | 214.7 | 83.5 | ||||||||||||||||||||
5 | — | — | 292.3 | 54.1 | 282.4 | 59.6 | 271.8 | 66.6 | 258.6 | 74.1 | 244.7 | 83.9 |
SLG 120-40(R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 60.5 | 21.4 | 53.5 | 25.1 | 50.7 | 27.8 | 46.0 | 30.6 | 40.1 | 34.2 | 34.4 | 37.5 | ||||||||||||||||||||
-15 | 75.6 | 21.9 | 65.8 | 25.3 | 63.7 | 28.4 | 56.8 | 31.1 | 49.4 | 35.2 | 44.1 | 38.3 | ||||||||||||||||||||
-10 | 93.5 | 22.4 | 82.2 | 26.1 | 76.9 | 29.0 | 69.9 | 31.7 | 63.0 | 35.9 | 56.2 | 39.2 | ||||||||||||||||||||
-5 | 111.3 | 22.9 | 99.3 | 26.9 | 92.6 | 29.8 | 85.2 | 32.6 | 77.2 | 36.5 | 68.4 | 40.0 | ||||||||||||||||||||
0 | — | — | 119.2 | 27.9 | 112.4 | 30.5 | 103.6 | 33.2 | 94.3 | 37.1 | 87.4 | 40.8 | ||||||||||||||||||||
5 | — | — | 143.3 | 28.9 | 131.9 | 31.1 | 123.6 | 34.2 | 113.9 | 37.5 | 102.2 | 41.5 |
SLG 120-40 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 74.3 | 22.9 | 72.5 | 27.9 | 69.8 | 31.2 | 65.8 | 35.2 | 60.2 | 38.7 | 58.5 | 44.5 | ||||||||||||||||||||
-15 | 88.8 | 23.1 | 85.4 | 28.2 | 82.0 | 31.5 | 77.4 | 35.4 | 71.6 | 39.0 | 70.4 | 44.9 | ||||||||||||||||||||
-10 | 104.9 | 23.5 | 100.0 | 28.5 | 96.1 | 31.6 | 90.9 | 35.7 | 84.7 | 39.1 | 82.9 | 45.0 | ||||||||||||||||||||
-5 | 122.4 | 23.6 | 116.0 | 28.9 | 111.7 | 31.9 | 106.3 | 35.9 | 99.7 | 39.6 | 95.0 | 45.3 | ||||||||||||||||||||
0 | — | — | 133.5 | 29.2 | 128.5 | 32.1 | 123.3 | 36.0 | 116.3 | 40.0 | 111.4 | 45.1 | ||||||||||||||||||||
5 | — | — | 151.7 | 29.3 | 146.5 | 32.2 | 141.0 | 36.0 | 134.2 | 40.1 | 127.0 | 45.4 |
SLG 290-100(R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 147.0 | 49.9 | 130.0 | 58.5 | 123.1 | 64.8 | 111.8 | 71.4 | 97.4 | 79.7 | 83.6 | 87.5 | ||||||||||||||||||||
-15 | 183.8 | 51.0 | 159.9 | 59.1 | 154.8 | 66.2 | 138.1 | 72.5 | 120.1 | 82.0 | 107.0 | 89.2 | ||||||||||||||||||||
-10 | 227.1 | 52.2 | 199.6 | 60.8 | 186.8 | 67.7 | 169.7 | 74.0 | 153.0 | 83.7 | 136.5 | 91.5 | ||||||||||||||||||||
-5 | 270.4 | 53.3 | 241.2 | 62.8 | 225.0 | 69.4 | 207.1 | 76.0 | 187.7 | 85.2 | 166.1 | 93.2 | ||||||||||||||||||||
0 | — | — | 289.6 | 65.1 | 273.1 | 71.1 | 251.6 | 77.4 | 229.2 | 86.6 | 212.3 | 95.2 | ||||||||||||||||||||
5 | — | — | 348.1 | 67.4 | 320.3 | 72.5 | 300.3 | 79.7 | 276.7 | 87.5 | 248.3 | 96.6 |
SLG 290-100 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 180.5 | 53.3 | 176.2 | 65.1 | 169.5 | 72.8 | 159.7 | 82.0 | 146.2 | 90.3 | 142.2 | 103.8 | ||||||||||||||||||||
-15 | 215.7 | 53.9 | 207.6 | 65.7 | 199.3 | 73.4 | 188.1 | 82.6 | 173.9 | 90.9 | 170.9 | 104.7 | ||||||||||||||||||||
-10 | 254.9 | 54.8 | 243.0 | 66.5 | 233.5 | 73.7 | 220.9 | 83.2 | 205.9 | 91.2 | 201.4 | 105.0 | ||||||||||||||||||||
-5 | 297.3 | 55.1 | 281.8 | 67.4 | 271.3 | 74.3 | 258.2 | 83.7 | 242.3 | 92.3 | 230.7 | 105.5 | ||||||||||||||||||||
0 | — | — | 324.2 | 68.0 | 312.1 | 74.8 | 299.7 | 84.0 | 282.6 | 93.2 | 270.7 | 105.2 | ||||||||||||||||||||
5 | — | — | 368.5 | 68.2 | 356.0 | 75.1 | 342.6 | 84.0 | 326.1 | 93.5 | 308.5 | 105.8 |
SLG 140-50 (R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 70.8 | 25.1 | 62.6 | 29.4 | 59.3 | 32.5 | 53.9 | 35.9 | 46.9 | 40.0 | 40.3 | 43.9 | ||||||||||||||||||||
-15 | 88.6 | 25.6 | 77.0 | 29.7 | 74.6 | 33.3 | 66.5 | 36.4 | 57.9 | 41.2 | 51.6 | 44.8 | ||||||||||||||||||||
-10 | 109.4 | 26.2 | 96.2 | 30.5 | 90.0 | 34.0 | 81.8 | 37.2 | 73.7 | 42.0 | 65.8 | 45.9 | ||||||||||||||||||||
-5 | 130.3 | 26.8 | 116.2 | 31.5 | 108.4 | 34.8 | 99.8 | 38.2 | 90.4 | 42.8 | 80.1 | 46.8 | ||||||||||||||||||||
0 | — | — | 139.5 | 32.7 | 131.6 | 35.7 | 121.2 | 38.9 | 110.4 | 43.5 | 102.3 | 47.8 | ||||||||||||||||||||
5 | — | — | 167.8 | 33.8 | 154.4 | 36.4 | 144.7 | 40.0 | 133.3 | 43.9 | 119.7 | 48.5 |
SLG 140-50 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 87.0 | 26.8 | 84.9 | 32.7 | 81.7 | 36.6 | 77.0 | 41.2 | 70.5 | 45.4 | 68.5 | 52.1 | ||||||||||||||||||||
-15 | 103.9 | 27.1 | 100.0 | 33.0 | 96.0 | 36.9 | 90.6 | 41.5 | 83.8 | 45.6 | 82.4 | 52.6 | ||||||||||||||||||||
-10 | 122.9 | 27.5 | 117.1 | 33.4 | 112.5 | 37.0 | 106.5 | 41.8 | 99.2 | 45.8 | 97.1 | 52.7 | ||||||||||||||||||||
-5 | 143.3 | 27.6 | 135.8 | 33.8 | 130.8 | 37.3 | 124.4 | 42.0 | 116.8 | 46.4 | 111.2 | 53.0 | ||||||||||||||||||||
0 | — | — | 156.2 | 34.1 | 150.4 | 37.6 | 144.4 | 42.2 | 136.2 | 46.8 | 130.5 | 52.8 | ||||||||||||||||||||
5 | — | — | 177.6 | 34.3 | 171.6 | 37.7 | 165.1 | 42.2 | 157.1 | 46.9 | 148.7 | 53.1 |
SLG 320-110 (R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 162.2 | 55.1 | 143.4 | 64.5 | 135.9 | 71.5 | 123.3 | 78.8 | 107.5 | 88.0 | 92.3 | 96.5 | ||||||||||||||||||||
-15 | 202.8 | 56.3 | 176.4 | 65.2 | 170.8 | 73.1 | 152.3 | 80.1 | 132.6 | 90.5 | 118.1 | 98.4 | ||||||||||||||||||||
-10 | 250.6 | 57.6 | 220.3 | 67.1 | 206.1 | 74.7 | 187.3 | 81.6 | 168.8 | 92.4 | 150.6 | 100.9 | ||||||||||||||||||||
-5 | 298.4 | 58.9 | 266.1 | 69.3 | 248.3 | 76.6 | 228.5 | 83.9 | 207.1 | 94.0 | 183.3 | 102.8 | ||||||||||||||||||||
0 | — | — | 319.5 | 71.8 | 301.4 | 78.5 | 277.6 | 85.4 | 252.9 | 95.6 | 234.3 | 105.1 | ||||||||||||||||||||
5 | — | — | 384.1 | 74.4 | 353.5 | 80.1 | 331.4 | 88.0 | 305.3 | 96.5 | 274.0 | 106.6 |
SLG 320-110 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 199.2 | 58.9 | 194.4 | 71.8 | 187.0 | 80.4 | 176.3 | 90.5 | 161.4 | 99.7 | 157.0 | 114.5 | ||||||||||||||||||||
-15 | 238.0 | 59.5 | 229.1 | 72.5 | 219.9 | 81.0 | 207.5 | 91.1 | 191.9 | 100.3 | 188.6 | 115.5 | ||||||||||||||||||||
-10 | 281.3 | 60.4 | 268.1 | 73.4 | 257.6 | 81.3 | 243.8 | 91.8 | 227.2 | 100.6 | 222.2 | 115.8 | ||||||||||||||||||||
-5 | 328.1 | 60.8 | 310.9 | 74.4 | 299.4 | 82.0 | 284.9 | 92.4 | 267.4 | 101.9 | 254.6 | 116.4 | ||||||||||||||||||||
0 | — | — | 357.8 | 75.0 | 344.4 | 82.6 | 330.7 | 92.7 | 311.8 | 102.8 | 298.7 | 116.1 | ||||||||||||||||||||
5 | — | — | 406.6 | 75.3 | 392.9 | 82.9 | 378.1 | 92.7 | 359.8 | 103.2 | 340.4 | 116.8 |
SLG 190-65(R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 97.4 | 33.1 | 86.1 | 38.8 | 81.6 | 42.9 | 74.1 | 47.3 | 64.5 | 52.8 | 55.4 | 58.0 | ||||||||||||||||||||
-15 | 121.8 | 33.8 | 105.9 | 39.1 | 102.6 | 43.9 | 91.5 | 48.1 | 79.6 | 54.3 | 70.9 | 59.1 | ||||||||||||||||||||
-10 | 150.5 | 34.6 | 132.3 | 40.3 | 123.8 | 44.8 | 112.5 | 49.0 | 101.4 | 55.5 | 90.4 | 60.6 | ||||||||||||||||||||
-5 | 179.2 | 35.3 | 159.8 | 41.6 | 149.1 | 46.0 | 137.2 | 50.4 | 124.3 | 56.4 | 110.1 | 61.8 | ||||||||||||||||||||
0 | — | — | 191.9 | 43.1 | 181.0 | 47.1 | 166.7 | 51.3 | 151.9 | 57.4 | 140.7 | 63.1 | ||||||||||||||||||||
5 | — | — | 230.7 | 44.7 | 212.3 | 48.1 | 199.0 | 52.8 | 183.3 | 58.0 | 164.5 | 64.0 |
SLG 190-65 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 119.6 | 35.3 | 116.7 | 43.1 | 112.3 | 48.3 | 105.8 | 54.3 | 96.9 | 59.9 | 94.2 | 68.8 | ||||||||||||||||||||
-15 | 142.9 | 35.7 | 137.5 | 43.5 | 132.0 | 48.6 | 124.6 | 54.7 | 115.2 | 60.2 | 113.3 | 69.4 | ||||||||||||||||||||
-10 | 168.9 | 36.3 | 161.0 | 44.1 | 154.7 | 48.8 | 146.4 | 55.1 | 136.4 | 60.4 | 133.5 | 69.5 | ||||||||||||||||||||
-5 | 197.0 | 36.5 | 186.7 | 44.7 | 179.8 | 49.2 | 171.1 | 55.5 | 160.6 | 61.2 | 152.9 | 69.9 | ||||||||||||||||||||
0 | — | — | 214.8 | 45.0 | 206.8 | 49.6 | 198.6 | 55.7 | 187.2 | 61.8 | 179.4 | 69.7 | ||||||||||||||||||||
5 | — | — | 244.2 | 45.2 | 235.9 | 49.8 | 227.0 | 55.7 | 216.1 | 61.9 | 204.4 | 70.1 |
SLG 350-120 (R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 177.4 | 60.2 | 156.9 | 70.6 | 148.6 | 78.2 | 134.9 | 86.2 | 117.6 | 96.2 | 100.9 | 105.6 | ||||||||||||||||||||
-15 | 221.8 | 61.6 | 192.9 | 71.3 | 186.8 | 79.9 | 166.6 | 87.6 | 145.0 | 99.0 | 129.2 | 107.6 | ||||||||||||||||||||
-10 | 274.1 | 63.0 | 240.9 | 73.4 | 225.4 | 81.7 | 204.9 | 89.3 | 184.7 | 101.1 | 164.7 | 110.4 | ||||||||||||||||||||
-5 | 326.4 | 64.4 | 291.0 | 75.8 | 271.6 | 83.8 | 249.9 | 91.7 | 226.5 | 102.8 | 200.5 | 112.5 | ||||||||||||||||||||
0 | — | — | 349.5 | 78.6 | 329.6 | 85.8 | 303.7 | 93.4 | 276.6 | 104.5 | 256.2 | 114.9 | ||||||||||||||||||||
5 | — | — | 420.2 | 81.3 | 386.6 | 87.6 | 362.5 | 96.2 | 334.0 | 105.6 | 299.7 | 116.6 |
SLG 350-120 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 217.9 | 64.4 | 212.6 | 78.6 | 204.6 | 87.9 | 192.8 | 99.0 | 176.5 | 109.0 | 171.7 | 125.3 | ||||||||||||||||||||
-15 | 260.3 | 65.1 | 250.5 | 79.3 | 240.5 | 88.6 | 227.0 | 99.7 | 209.9 | 109.7 | 206.3 | 126.3 | ||||||||||||||||||||
-10 | 307.7 | 66.1 | 293.3 | 80.3 | 281.8 | 88.9 | 266.6 | 100.4 | 248.5 | 110.1 | 243.1 | 126.7 | ||||||||||||||||||||
-5 | 358.8 | 66.4 | 340.1 | 81.3 | 327.5 | 89.6 | 311.6 | 101.1 | 292.4 | 111.4 | 278.4 | 127.4 | ||||||||||||||||||||
0 | — | — | 391.3 | 82.0 | 376.7 | 90.3 | 361.7 | 101.4 | 341.1 | 112.5 | 326.8 | 127.0 | ||||||||||||||||||||
5 | — | — | 444.7 | 82.4 | 429.7 | 90.7 | 413.5 | 101.4 | 393.6 | 112.8 | 372.3 | 127.7 |
SLG 210-70 (R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 103.3 | 35.1 | 91.4 | 41.1 | 86.5 | 45.5 | 78.5 | 50.2 | 68.5 | 56.0 | 58.8 | 61.5 | ||||||||||||||||||||
-15 | 129.2 | 35.9 | 112.4 | 41.5 | 108.8 | 46.6 | 97.0 | 51.0 | 84.4 | 57.6 | 75.2 | 62.7 | ||||||||||||||||||||
-10 | 159.6 | 36.7 | 140.3 | 42.7 | 131.3 | 47.6 | 119.3 | 52.0 | 107.5 | 58.8 | 95.9 | 64.3 | ||||||||||||||||||||
-5 | 190.1 | 37.5 | 169.5 | 44.1 | 158.1 | 48.8 | 145.5 | 53.4 | 131.9 | 59.9 | 116.8 | 65.5 | ||||||||||||||||||||
0 | — | — | 203.5 | 45.7 | 191.9 | 50.0 | 176.8 | 54.4 | 161.1 | 60.9 | 149.2 | 66.9 | ||||||||||||||||||||
5 | — | — | 244.7 | 47.4 | 225.1 | 51.0 | 211.1 | 56.0 | 194.5 | 61.5 | 174.5 | 67.9 |
SLG 210-70 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 126.9 | 37.5 | 123.8 | 45.7 | 119.1 | 51.2 | 112.3 | 57.6 | 102.8 | 63.5 | 100.0 | 72.9 | ||||||||||||||||||||
-15 | 151.6 | 37.9 | 145.9 | 46.1 | 140.0 | 51.6 | 132.2 | 58.0 | 122.2 | 63.9 | 120.1 | 73.6 | ||||||||||||||||||||
-10 | 179.2 | 38.5 | 170.8 | 46.8 | 164.1 | 51.8 | 155.2 | 58.4 | 144.7 | 64.1 | 141.5 | 73.8 | ||||||||||||||||||||
-5 | 208.9 | 38.7 | 198.0 | 47.4 | 190.7 | 52.2 | 181.5 | 58.8 | 170.3 | 64.9 | 162.1 | 74.2 | ||||||||||||||||||||
0 | — | — | 227.8 | 47.8 | 219.3 | 52.6 | 210.6 | 59.0 | 198.6 | 65.5 | 190.3 | 74.0 | ||||||||||||||||||||
5 | — | — | 259.0 | 48.0 | 250.2 | 52.8 | 240.8 | 59.0 | 229.2 | 65.7 | 216.8 | 74.4 |
SLG 370-130(R404A) | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 187.6 | 63.7 | 165.8 | 74.6 | 157.1 | 82.7 | 142.6 | 91.1 | 124.3 | 101.7 | 106.7 | 111.6 | ||||||||||||||||||||
-15 | 234.5 | 65.1 | 204.0 | 75.4 | 197.5 | 84.5 | 176.1 | 92.6 | 153.3 | 104.6 | 136.6 | 113.8 | ||||||||||||||||||||
-10 | 289.8 | 66.6 | 254.7 | 77.6 | 238.3 | 86.3 | 216.6 | 94.4 | 195.2 | 106.8 | 174.2 | 116.7 | ||||||||||||||||||||
-5 | 345.0 | 68.0 | 307.7 | 80.1 | 287.1 | 88.5 | 264.2 | 97.0 | 239.4 | 108.7 | 212.0 | 118.9 | ||||||||||||||||||||
0 | — | — | 369.4 | 83.0 | 348.5 | 90.7 | 321.0 | 98.8 | 292.4 | 110.5 | 270.9 | 121.5 | ||||||||||||||||||||
5 | — | — | 444.2 | 86.0 | 408.7 | 92.6 | 383.2 | 101.7 | 353.0 | 111.6 | 316.8 | 123.3 |
SLG 370-130 (R404A) ECO | ||||||||||||||||||||||||||||||||
Tc | 20 | 30 | 35 | 40 | 45 | 50 | ||||||||||||||||||||||||||
Te | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | Qo | Pa | ||||||||||||||||||||
-20 | 230.3 | 68.0 | 224.8 | 83.0 | 216.2 | 92.9 | 203.8 | 104.6 | 186.6 | 115.2 | 181.5 | 132.4 | ||||||||||||||||||||
-15 | 275.2 | 68.8 | 264.9 | 83.8 | 254.2 | 93.7 | 240.0 | 105.4 | 221.9 | 116.0 | 218.1 | 133.5 | ||||||||||||||||||||
-10 | 325.3 | 69.9 | 310.0 | 84.9 | 297.9 | 94.0 | 281.9 | 106.1 | 262.7 | 116.3 | 257.0 | 133.9 | ||||||||||||||||||||
-5 | 379.4 | 70.2 | 359.5 | 86.0 | 346.2 | 94.8 | 329.4 | 106.8 | 309.1 | 117.8 | 294.3 | 134.6 | ||||||||||||||||||||
0 | — | — | 413.7 | 86.7 | 398.2 | 95.5 | 382.3 | 107.2 | 360.5 | 118.9 | 345.4 | 134.3 | ||||||||||||||||||||
5 | — | — | 470.2 | 87.1 | 454.2 | 95.9 | 437.2 | 107.2 | 416.1 | 119.3 | 393.6 | 135.0 |
Recommended Products