2600 flat flower base cold storage equipment configuration scheme sharing

August 8, 2024

2600 flat flower base cold storage equipment configuration scheme sharing

 

  Flowers are a kind of time-dependent and seasonal plants with certain growth conditions. Flowers leave the mother, lose the nutrient supply, will soon wither, lose fresh color. From harvest to commodity until the loss of use value, the whole process is shorter than fruits and vegetables, easy to rot, and the post-harvest loss rate is about 20%, much higher than fruit and vegetable products. Many flowers choose to use fresh cold storage to store flowers.

  Moreover, many flowers not only have ornamental value, but also medicinal value! For example, peony, peony root can be medicated, called "Paeonia", with analgesia, spasmodic, remove blood stasis, menstrual function; The oil content of peony seeds is about 25%, which can be used in making soap and paint.

  The project is located in Tianjin, Kubao refrigeration specially configured for peony solution, divided into 5 sets of refrigeration systems.
  01# refrigeration system, the size of the warehouse 19.4m×16.4m, the temperature of the warehouse 2℃ ~ 4℃, the storage capacity of 22T, to   meet the processing capacity of 7.5T, the purchase temperature of 33℃ products, cooling for 4h, to reach the shipping temperature of 18℃.
  02# refrigeration system, including processing room (83.4m×16.4m×4m), buffer room (87.8m×2.5m×5m), storage temperature 18℃.
  03# refrigeration system, including absorbent fresh-keeping room (31.4m×8.9m×4m), fresh-keeping and shipment room (13.4m×8.9m×4m), storage temperature 2℃ ~ 4℃.
  04# refrigeration system, including 2 air conditioning warehouse, single room 13.4m×8.9m×4m, fresh storage room (9.4m×8.9m×4m), the temperature in the warehouse 2℃ ~ 4℃.
  05# The refrigeration system is a cold storage, the size is 3.4m×8.9m×4m, and the temperature in the storage is -15℃.

 

 

 

  01# Refrigeration system

  Refrigeration unit selection: Refrigeration unit selection of KUB refrigeration box type air cooled 2 parallel unit configuration, unit model is: XJQ2-60GCY, compressor model: ZB220KQE, refrigerant R507, evaporation temperature -5℃, condensing temperature 45℃, cooling capacity 128KW, power 49.7kw, meet the requirements of 01# refrigeration system.

Evaporator selection: Adopt KUB brand cold air model number: DL-35/160, cooling capacity of 34.6KW, equipped with 4 chillers to meet the requirements of the system.

  02# Refrigeration system
Refrigeration unit selection: The refrigeration unit selects the KUB refrigeration model: LSLG75AS unit, the Hanzhong semi-closed screw compressor model: SC2-300B compressor, refrigerant R507. The evaporation temperature is 0℃, the condensation temperature is 45℃, the cooling capacity is 226.7KW, the power is 82.2kw, which meets the requirements of 02# refrigeration system.

Evaporator selection: Processing room and buffer room chiller adopts fixed value double-side air chiller model: GSL-12.6/60, cooling capacity 12.6KW, 15 processing room, 5 buffer room.

  03# Refrigeration system
Refrigeration unit selection: Refrigeration unit selection of KUB refrigeration box type air-cooled 2 parallel unit configuration, unit model is: XJQ2-44GCY, using Emerson scroll compressor model: ZB150KQE, evaporation temperature -5℃, condensing temperature 45℃, cooling capacity of 82KW, power 31kw, to meet the requirements of 03# refrigeration system.
Evaporator selection: Water absorption fresh-keeping room cooler adopts KUB brand cold air model No. : DL-17/80, cooling capacity: 17KW, 4 sets; The fresh-keeping and shipping room chiller adopts KUB brand side outlet air chiller model: XKDL-23/105, cooling capacity: 23KW, equipped with 2 sets.

  04# Refrigeration system
Refrigeration unit selection: The refrigeration unit is equipped with two parallel chiller sets of KUB refrigeration box air cooling unit, the model of the unit is: LSQ60AD, the model of Emerson scroll compressor is: ZB220KQE, the evaporation temperature is -10℃, the condensation temperature is 45℃, the cooling capacity is 107KW, the power is 49.7kw, which meets the 04# requirements of the refrigeration system. Secondary refrigerant indirect refrigeration.
Evaporator selection: Fresh-keeping and shipping room chiller adopts brand cold air model No. : ZDL-17/80, cooling capacity: 17KW, equipped with 2 sets.

  05# refrigeration system
Refrigeration unit selection: Refrigeration unit selection of KUB refrigeration piston parallel unit configuration, unit model: XJB2-68DBY, the use of Bitzer semi-closed compressor model: Two 6GE-34Y-40P compressors, evaporation temperature -25℃, condensing temperature 45℃, cooling capacity 73.2kw, power 43.6kw, meet the 05# requirements of the refrigeration system.
Evaporator selection: The processing room chiller adopts KUB brand fixed value double-side air chiller model: DD-44/250, cooling capacity 37.5KW, configured with 2 sets.。

Shanghai KUB Refrigeration Equipment Co., Ltd.

 

 

Free Call Video Chat

 

 

 

Address : No. 328 on the 4th plant hengyong Road, Jiading District, Shanghai
Factory Address : No. 328 on the 4th plant hengyong Road, Jiading District, Shanghai
Work Time : 8:30-17:30(Beijing time)
Phone :

86-021 -63184860-17(Work Time)

86--13916495206(Nonworking time)

Fax : 86-021-53750132
Email : lucy@shkubao.com

 

Customer Manager
Mr mick Cai
Phone : +86 13588563336
WhatsApp : +86 13588563336
Skype : kub.mick
WeChat : CP9301
Email : kub02@shkubao.com

 

Miss. Mophy Mao
Phone : +86 15001938306
WhatsApp : +86 15001938306
WeChat : kub-maomao
Email : kub@shhkubao.cn