NT2178GK 1HP R404A Cold Storage Fridge Polynomial Equation
Contact me for free samples and coupons.
Whatsapp:0086 18588475571
Wechat: 0086 18588475571
Skype: sales10@aixton.com
If you have any concern, we provide 24-hour online help.
xVoltage | 220-240V/50Hz | Refrigerant | R404A |
---|---|---|---|
After-sales Service Provided | Online Support | Packing | Wooden Case |
Highlight | R404A Cold Storage Fridge,1HP Cold Storage Fridge,NT2178GK Cold Storage Fridge |
Rated Points
Condensing Temperature | Evaporating Temperature | Cooling Capacity | Power Consumption | Current | Gas Flow Rate | Efficiency | |||
54.40°C | -23.30°C | 804 W | 564 W | 2.56 A | 18.61 kg/h | 1.43 W/W |
Test Condition: ASHRAELBP32, Fan/NotControled/220, Return Gas 32.2°C, Evaporation -23.30°C, Condensing 54.40°C, Ambient 32.2°C , Liquid 32.2°C, Subcooling 22.2K. Data in accordance to EN
12900:2013 and AHRI 540:2015 polynomial equation and uncertainty guidance.
Performance Curve Data
Condensing Temperature 35°C
Evaporating Temperature °C |
Cooling Capacity W |
Power W | Current A | Gas Flow Rate kg/h |
Efficiency W/W |
-40 | 355 | 355 | 1.67 | 8.15 | 1 |
-35 | 501 | 411 | 1.89 | 11.53 | 1.22 |
-30 | 675 | 466 | 2.12 | 15.58 | 1.45 |
-25 | 876 | 520 | 2.37 | 20.30 | 1.68 |
-20 | 1103 | 574 | 2.62 | 25.71 | 1.92 |
-15 | 1357 | 627 | 2.89 | 31.81 | 2.16 |
-10 | 1636 | 679 | 3.17 | 38.61 | 2.41 |
Test Condition: ASHRAELBP32, Fan/NotControled/220, Return Gas 32.2°C, Ambient 32.2°C , Liquid 32.2°C. Data in accordance to EN 12900:2013 and AHRI 540:2015 polynomial equation and uncertainty guidance.
Condensing Temperature 45°C
Evaporating Temperature °C |
Cooling Capacity W |
Power W | Current A | Gas Flow Rate kg/h |
Efficiency W/W |
-35 | 440 | 400 | 1.86 | 10.10 | 1.1 |
-30 | 609 | 465 | 2.13 | 14.03 | 1.31 |
-25 | 806 | 531 | 2.41 | 18.65 | 1.52 |
-20 | 1032 | 599 | 2.71 | 23.99 | 1.72 |
-15 | 1285 | 667 | 3.02 | 30.06 | 1.93 |
-10 | 1564 | 736 | 3.35 | 36.85 | 2.12 |
Test Condition: ASHRAELBP32, Fan/NotControled/220, Return Gas 32.2°C, Ambient 32.2°C , Liquid 32.2°C. Data in accordance to EN 12900:2013 and AHRI 540:2015 polynomial equation and uncertainty guidance.
Condensing Temperature 55°C
Evaporating Temperature °C |
Cooling Capacity W |
Power W | Current A | Gas Flow Rate kg/h |
Efficiency W/W |
-30 | 539 | 462 | 2.13 | 12.39 | 1.17 |
-25 | 731 | 537 | 2.45 | 16.87 | 1.36 |
-20 | 952 | 615 | 2.79 | 22.09 | 1.55 |
-15 | 1202 | 695 | 3.15 | 28.07 | 1.73 |
-10 | 1480 | 779 | 3.52 | 34.80 | 1.9 |
Test Condition: ASHRAELBP32, Fan/NotControled/220, Return Gas 32.2°C, Ambient 32.2°C , Liquid 32.2°C. Data in accordance to EN 12900:2013 and AHRI 540:2015 polynomial equation and uncertainty guidance.
External Dimensions